Table 1-1. Duct Heaters (DH)
KW
VOLT/
APERTURE DIMENSIONS
NO.
SPACE SERVED
REQD PHASE CFM
WIDTH X HEIGHT
DH-1
Preheater/Accommodations Air
19.10
240/3
1200
49.125 x 23.875
Preheat Thermostat Settings;
inch
Thermostat 1-48
F
Thermostat 2-42
F
DH-2
Pilothouse
12.00
240/3
1200
24W x 10H
DH-3
Galley (Make Up Air) Port Side
35.00
240/3
1725
24W x 10H
DH-4
Chief Engineer Stateroom
0.50
110/1
140
6W x 6H
DH-5
Crew SR 01 Level
1.00
240/3
155
8W x 6H
DH-6
Crew SR 01 Level
0.50
110/1
150
8W x 6H
DH-7
Crew SR 01 Level
1.00
240/3
200
8W x 6H
DH-8
Crew SR 01 Level
1.75
240/3
390
10W x 8H
DH-9
Laundry Room
0.50
240/3
65
12W x 8H
DH-10
Captain Stateroom
1.00
240/3
170
6W x 6H
DH-11
Mess Room
2.00
240/3
705
18W x 10H
DH-12
Galley
0.50
240/3
200
24W x 18H
DH-12A
Galley
0.50
240/3
200
24W x 18H
DH-13
Pantry
1.50
240/3
250
10W x 6H
DH-14
Arms Control Room
0.50
110/1
85
6W x 4H
DH-15
Sick Bay
1.50
110/1
200
8W x 6H
DH-16
Recreation Room
1.00
240/3
330
12W x 6H
DH-17
Engine Control Room
1.00
240/3
100
4W x 4H