Table 2-2. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
STEP 2.
Check for air in the fuel system.
Bleed the fuel system. Refer to PMCS, Item 12.
STEP 3.
Check for poor quality fuel.
a.
Drain and flush the fuel supply tanks.
b.
Replenish with clean fuel.
STEP 4.
Check for overloaded engine.
Verify the generator output does not exceed rating. Refer to the generator set data tag for rating.
STEP 5.
Check for malfunctioning injectors.
Replace injectors (para. 2-39).
9. Generator will not pull the load (low engine power).
STEP 1.
Check for overloaded engine.
Verify that generator set rating is not being exceeded.
STEP 2.
Check to see if fuel control lever is not moving to full speed.
Check for full stop-to-stop travel as follows:
a.
Place-the run-off toggle switch in the "RUN" position and the idle normal toggle switch in the "IDLE"
position.
b.
Press in on the permissive start button to activate the solenoid to the "HIGH IDLE" position.
CAUTION
Make sure that the solenoid is allowed to move to its full travel position when
activated, otherwise the pull coil will be damaged within 30-40 seconds.
NOTE
Pull in requires 19 amperes.
Hold in requires .5 amperes.
c.
Loosen the locknut and adjust the linkage to obtain full stop-to-stop travel (para. 3-12).
STEP 3.
Check to see if fuel pump timing is correct.
Visually verify fuel pump timing marks are aligned (para. 2-33).
2-26