TM 55-1905-223-24-4
Table 2-1. Preventive Maintenance Checks and Services (PMCS)-CONT
E - Every 20 hours
W - Weekly
Q - Quarterly
S - Semiannually
A - Annually
B - Biennially
INTERVAL
ITEM
ITEMS TO BE
Procedures
NO.
INSPECTED/SERVICED
EWQ
S
A
B
6.
Oil filter - CONT
Operate the engine and inspect for leaks at the filter and sump
CONT
pump suction line.
To check the oil level:
a. Shut off the engine.
b. Allow oil to drain down (about 5 minutes).
c. Check oil level.
Air intake
Inspect the intake piping for damage, cracked hoses, and loose clamps.
7.
CAUTION
Never operate engine without an air cleaner.
For replacement of air cleaner (para. 2-25).
8.
Wiring
Overall inspection. Look for discolored
connections that indicate heating due to poor
electrical connection. The inspection should
include: circuit breakers, transfer switch
connections, and generator conduit box wiring.
9.
Engine mounts
Check the frame rail mounting bolts and the engine mounts for tightness.
Change 1