Click here to make tpub.com your Home Page

Page Title: Replace/Repair Motor, Electric, Alternating Current (Supply Fan #4).
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 55-1905-223-24-17
2-26. Replace/Repair Motor, Electric, Alternating Current (Supply Fan #4). (FIGURE 2-16)
This task covers:
a. Removal,
b. Repair,
c. Replacement.
INITIAL SETUP
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switch OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
Puller 5120-00-516-3120
See TM 55-1905-223-10 for HVAC systems
Hydraulic press PN 2009-13
operation and equipment location.
Materials/Parts
AC electric motor
P/N 355790Y606
Annular ball bearing P/N 203
Bearing P/N 205
Tag, Item 1, Appendix C
Grease, Item 2, Appendix C
WARNING
Make sure electrical power is OFF to avoid personal injury.
REMOVAL
a. Remove weather cover from fan assembly for access to motor (paragraph 2-25).
b. Tag and disconnect electrical wiring in motor terminal box (9, FIGURE 2-16).
c. Refer to paragraph 2-25 and FIGURE 2-15, and remove the motor as follows:
(1)
Loosen tension on V-belt. Remove belt from around motor pulley (3, FIGURE 2-15).
(2)
Use a puller and remove the motor pulley (3) and machine key (4).
(3)
Remove motor mounting bolt, nut, and lockwasher assemblies (6).
(4)
Remove the motor (5) from the motor base (7).
2-71

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business